Panasonic Elite PACi Twin/Triple/Quad System 7.1kW – 14.0kW

PACi Elite Twin, Triple and Double-Twin System from 7.1 to 14.0 kW

Up to 4 indoor units can be connected to the same outdoor unit. Panasonic’s PACi units 71, 100, 125 and 140 can be installed as twin, triple and double-twin systems. The indoor units can be combined as per the selection table. The operation will always be simultaneous. All the indoor units will work with the same settings.

SINGLE/SIMULTANEOUS OPERATION SYSTEM COMBINATIONS

Indoor size 7.1 kW 10.0 kW 12.5 kW 14.0 kW
3.6 kW Twin Triple Double-Twin
4.5 kW Triple
5.0 kW Twin Triple
6.0 kW Twin
7.1 kW Twin

 

INDOOR UNIT RANGE

Capacity Walls 4 Way 60×60 Cassette
4 Way 90×90 Cassette
Low Static Pressure Hide Away High Static Pressure Hide Away Ceiling

3.6 kW S-36PK1E5A S-36PY2E5A S-36PU2E5A S-36PN1E5A S-36PF1E5A S-36PT1E5A
4.6 kW S-45PK1E5A S-45PY1E5A S-45PU2E5A S-45PN1E5A S-45PF1E5A S-45PT1E5A
5.0 kW S-50PK1E5A S-50PY1E5A S-50PU2E5A S-50PN1E5A S-50PF1E5A S-50PT1E5A
6.0 kW S-60PK1E5A S-60PU2E5A S-60PN1E5A S-60PF1E5A S-60PT1E5A
7.1 kW S-71PK1E5A S-71PU2E5A S-71PN1E5A S-71PF1E5A S-71PT1E5A

 

PIPING LENGTH

TWIN                                                                                TRIPLE                                                                       QUAD

  

Joint distribution (sold separately): A= CZ-P155BK1 / B= CZ-P3HPC2BM / C= CZ-P155BK1

 

Item Indoor unit combinations (see examples above) Equivalent lengths and height differences (m) for outdoor unit sizes from 7,1 to 14,0 kW
Twin Triple Double-Twin
Total pipe length L+L1+L2 L+L1+L2+L3 L+L1+L2+L3+L4+L5+L6 U-60/U-71: ≤ 50 m

U-100/125/140: ≤ 75 m

Maximum pipe length from outdoor unit to most distant indoor unit L + L1 or L + L2 L + L1 or L + L2 or L + L3 L + L1 + L3 or L + L1 + L4 or L + L2 + L5 or L + L2 +L6
Maximum branch pipe length L1 or L2 L1 or L2 or L3 L1+L3 or L1+L4 or L2+L5 or L2+L6 ≤ 15 m
Maximum branch pipe length differences L1 > L2

L1-L2

L1 > L2 > L3: L1-L2

L2-L3

L2+L6 (MAX)

L1+L3 (MIN):

(L2+L6)-(L1+L3)

≤ 10 m
Max. pipe length after frist branch (Double-Twin) L2 > L1: L2-L1 ≤ 10 m
Maximum pipe length differences of branch pipe 1 (Double-Twin) L4 > L3: L4-L3

L6 > L5: L6-L5

≤ 10 m
Height difference (outdoor unit located higher) H1 H1 H1 ≤ 30 m
Height difference (outdoor unit located higher) H1 H1 H1 ≤ 15 m
Height difference between indoor units H2 H2 or H3 or H4 H2 or H3 or H4 or H5 or H6 ≤ 0.5 m

 

Outdoor unit main pipe diameter (L) (mm) Indoor unit connection pipe diameter (L1, L2, L3, L4) (mm)
Unit type capacity 71-140 36 45 50 60 71
Liquid pipe (mm) Ø 9.52 Ø 6.35 Ø 6.35 Ø 6.35 Ø 9.52 Ø 9.52
Gas pipe (mm) Ø 15.88 Ø 12.70 Ø 12.70 Ø 12.70 Ø 15.88 Ø 15.88
Additional charge (g/m) 50 20 20 20 50 50

1. Total capacity of indoor unit connected after the branch

 

Refrigerant charging: For the twin connection, the amount of refrigerant required for pipe length 30 m has been included in this unit at the factory while that required for pipe length 20 m has been included for the Triple / Double-Twin connections.

No additional charge is required for the first 30 m pipe length in the case of the twin connection and for the first 20 m in the case of the Triple / Double-Twin connections.

Make additional charges by adding up pipe length in an order of main (L branch pipe), (L1, L2, L3 wide diameter) and then selecting the amount of refrigerant corresponding to the remaining (after 30 m for the Twin connection and after 20 m for the Triple / Double-Twin connections) liquid side pipe diameter and pipe length from the below table.